Description
VPIS for M.V. cubicles (switchgear)
DXN series of voltage presence indicating system (VPIS) indicates the voltage presence on M.V. cubicles by being installed on the capacitive dividers.



Product Features
- 3-phase live-voltage indicating system
- Can work with phase comparator for phase checking
- Wide-range 3kV- 40.5kV
- Working frequency 50/60Hz
- Threshold values for voltage presence indication: U>0.40 x Unmin
- Threshold values for voltage absence indication: U<0.15 x Unmax
- Divider capacitance 8pF or be specified by buyer
- Temperature range -25°C to +40°C
- Insulation strength: AC 2kV, 1min
- Product dimensions (W×H×D) 130x30x55mm
Technical Parameter
| Executive Standard | DL/T538-2006 |
| Working Frequency | 50Hz/60Hz |
| Nominal Voltage | 3-3.6kV |
| 6-7.2kV | |
| 10-12kV | |
| 20-24kV | |
| 35-40.5kV | |
| Divider Capacitance | 8pF,or customized by buyers |
| Threshold Values for Voltage Presence Indication | U>0.40 x Unmin |
| Threshold Values for Voltage Absence Indication | U<0.10 x Unmax |
| Working Temperature | -25℃ – +40℃ |
| Working Humidity | <95% |
| Insulation Strength | 2kV,1min |
| Protection Level | IP20 |
| Overall Dimension (WxHxD) | 130x30x55 mm |
| Mounting Dimension (WxHxD) | 105x25x52 mm |
接线示意图

| Marks | Definitions |
| Earth Terminal | |
| L3 | HV Phase L3, the input terminal for coupling signals |
| L2 | HV Phase L2, the input terminal for coupling signals |
| L1 | HV Phase L1, the input terminal for coupling signals |
Ordering Information

中文版